The
SATEC ezPACTM
SA300 Series Power Intelligence Unit is an advanced power
analysis and control device unmatched in the utility and
industrial environments.
The SATEC ezPACTM
SA300 Series are a fusion of many intelligent electronic
devices (IED) combined into one single powerful unit. The SATEC ezPACTM
SA300 Series unite Distributed Fault-Recording, Sequence of
Events (SOE), Revenue Metering, Power Quality, Back up to
Protection equipment and control devices to provide a complete
solution for substation and industrial automation.
The unique modular expansion chassis of the SATEC ezPACTM
SA300 Series assures the capability of meeting the needs of
today and the future by selecting different plug-in options for
multiple applications. The ezPACTM
allows a relatively low cost upgrade to be accomplished with
just minimal panel and wiring changes. Modular I/O design lets
you order a custom-made product according to your needs.
Upgradeable
Firmware
The SATEC SA300 uses flash memory for storing device
firmware that allows future upgrading of the device without
replacing any hardware component. You no longer have to replace
EPROM and remove from service. The new features can be easily
added to your device by simply replacing the firmware through a
local RS-232 port or Ethernet port.
Substation Automation Upgrade
The SATEC ezPACTM
SA300 Power Intelligence Unit is an ideal cost effective means
of automating an electrical substation. The SATEC ezPACTM
can be installed at a fraction of the cost and time involved in
replacing protection relays.
By adding one SATEC ezPACTM
Model on each feeder circuit, ALL the information needed for
substation automation is provided. The SATEC ezPACTM
SA300 extends the life expectancy of electromechanical relays
for many years to come by providing INFORMATION
lacking in these highly reliable devices without interfering in
the protection scheme.
The
SA300 combines in a single enclosure:
|
|
|
Distributed
Fault Recording Functions
include true digital fault recording, sequence of event
recording, and disturbance recording of four current channels for
up to 150 Amps of fault currents (30X). Four AC voltage channels
and DC measurement input channels are also included. Multiple ezPACTM
can cross trigger for up to 20 cycles of pre-fault information
for distributed recording. Fault information can be exported to
optional COMTRADE format via PAS software.
|
|
Precise
Sequence-of-Events Recorder (SOE) - Designed
for a electrical utility substation or plant environment to
record contact openings and closing of field devices such as
electromechanical and microprocessor controlled relays.16
digital inputs are provided and can easily expand up to a total
of 48 digital inputs (wet or dry type) with a 1 mSec time
resolution between events.
|
|
Power
Quality Analyzer - Advanced
power quality monitoring reporting as per IEEE 1159
classification. Report by exception with programmable thresholds
and hysteresis, ready-for-use reports; transients, impulses,
sags/swells, interruptions, inter-harmonics as per IEEE519,
frequency variations, volts unbalance.
|
|
High
Speed Sampling- The
utilization of the latest DSP technology and the innovative data
concept allow very long recording periods without compromising
the high level of accuracy. Simultaneous
sampling with individual A/D conversions assures no phase
differential for 12-channels of AC, one VDC and digital inputs
recording. Selectable simultaneous AC recording rate of 32, 64
and 128 samples per cycle; over 3 min of continuous recording
with a 5-Mbyte onboard expandable memory.
|
|
Long
Term Recording - For
data logging & trending, internal diagnostics events,
control events and I/O operations.
|
|
Fast
Data Logging Recorder - From
1/2 cycle RMS to 2-hour RMS envelopes are provided. Most useful
in quickly determining relay operation by recording the RMS
value of each cycle and displaying the entire trend when breaker
clears, resets, lockout or fails to operate; up to 20 pre-fault
cycles; programmable post fault on any internal and external
trigger condition.
|
|
Programmable
Controller Advanced
programmable logic makes it ideal for controlling multiple CAP
banks, Tap changes under load and alarming. Programmable 32
setpoints control, OR/AND logic, operate with release triggers,
thresholds with delays, relay control, event-driven data
recording.
|
|
Digital
Power Meter - You
can now eliminate the added cost of a multifunction digital
meter. Protection relays are poor substitutes for metering and
can be dangerous and misleading when high harmonic contents are
present in AC current or voltages typically found in
distribution circuits. Providing high accuracy True RMS values
for volts, amps, powers, power factors, unbalance, harmonic,
demands (predicted, fixed and sliding) and neutral current are
included.
|
|
Revenue
Accurate Billing Meets
ANSII C12.2 (0.2 class) Advanced Time-of Use feature for any
complex billing scheme is provided. Totalizing from multiple
energy and demand registers from energy pulses via external
watt-meters.
|
|
Directional
Harmonic Analyzer - Total
Harmonic Distortion for V&I and up to the 63rd.
Including directional power harmonics (Load or Source), power
factor, phasor diagram, symmetrical components.
|
|
External
Time Synchronization - provides
1 mSec time resolution via IRIG-B time-code input or GOES type
satellite clock.
|
|
Dual
Independent Power Supplies Primary
AC/DC and Secondary power supply provide continuous operation.
|
|
Memory
Expansion Card The
SATEC SA300 can be equipped with a 64/128-MByte
Expansion Memory plug-in module for long-term waveform and
data, trend recording.
|
|
AC/DC Inputs
The
SA300 is provided with a set of fully isolated AC/DC
inputs for a connection to the AC feeders and station battery:
|
|
|
Four
5.5 kV Galvanically Isolated AC voltage inputs - Up
to 690VAC direct input voltage.
|
|
Four
Galvanically Isolated AC current inputs - Includes
an extended input range up to ×3000% overload (10A/IEC or
20A/ANSI input currents, to 150 Amps fault currents).
|
|
A
second set of four Galvanically Isolated current inputs (Model
SA330 only) - In
addition to the high measurement CT above this additional set of
CT inputs (10A/IEC or 20A/ANSI input currents) is used for
precise energy metering
thus eliminating expensive revenue billing meters.
|
|
DC
voltage input - Used
for station battery
monitoring
(up to 300VDC). Set point triggers and alarming.
|
Digital and Analog I/O Options
The
SA300 has five I/O expansion slots for removable plug-in
I/O modules:
|
|
|
DI
- Digital inputs - 16
optically isolated inputs per module (one provided), up to 3
modules per device; options for dry contacts, 12V, 24V, 48V and
125V wet inputs; programmable de-bounce time from 1 ms to 1 sec;
quick linkage to Sequence-of-Events Recorder, Fault Recorder,
control setpoints, pulse counters and Energy/TOU subsystem.
|
|
RO
8 Relay Outputs - 6
Form A relays rated at 5 Amps @125VDC and two Form C relays for
energy pulsing are provided per module. Up to 4 modules per
device; programmed forunlatched, latched and pulse operations,
failsafe operation for alarm notifications; programmable pulse
width; direct remote relay control through communications.
|
|
AI/AO
- Four
optically isolated analog outputs and four optically isolated
inputs internal power supplies per module. Up to 4 modules per
device; options for 0-1mA, ±1mA, 0-20mA and 4-20mA
inputs and outputs; ×200% overload current for 0-1mA and
±1mA AI/AO.
|
Communications Options
The
SATEC SA300 includes FIVE independent communication ports
expandable to SEVEN:
|
|
|
Three
universal serial communications ports - Com
1 = (selectable RS-232, RS-422/RS-485) COM 2 = (RS-422/RS-485),
additional RS-485 port for remote display or external RTU.
Independent selectable up to 115,200 bps (includes Modbus RTU/ASCII
and DNP3.0 protocols).
|
|
USB
1.1 port 12
Mbps for fast local communications and data retrieving
|
|
Ethernet
10Base-T port - Modbus/TCP
and DNP3.0/TCP protocols, up to five non-intrusive simultaneous
connections, Telnet service port.
|
|
Embedded
56K modem (optional) - for
communications through public telephone lines (Modbus RTU/ASCII
and DNP3.0 protocols).
|
|
Infrared
port (optional) - (Modbus
RTU/ASCII and DNP3.0 protocols).
|
|
Auto
Alarm messages to Pager or E-mail
(notification of priority problems via dial-out modem or
Ethernet) coming soon.
|
Remote
Displays
The SA300 can be ordered with an optional bright LED
Remote Display Module (RDM). It has a RS485 port and communicate with
the SA300 through the Modbus RTU protocol. Remote
display can be located at distances of up to 0.5 km from the
device.
The RDM300 has three six-digit windows with bright red LEDs
well suited for direct sunlight applications. It allows the user
to view real-time RMS and harmonics measurements, status
indication parameters, and perform basic setup operations when
installing and servicing the device.
Device Models
The ezPACTM
SA300 Series production line includes two device models
|
|
SA320
- Power Quality model - offers all the ezPACTM
metering, control, and fault and event recording capabilities. Adds an EN50160 and IEEE 1159 power quality
recorder classifications and reports, and also EN50160 statistic acquisition and reports.
|
|
SA330
- Premium model Includes the standard 150A current inputs
for fault recording and adds to above additional four current
inputs (10A/20A) for revenue energy metering and management.
|
|
|
|
PM110
| PM130 PLUS
| PM172
| PM296/RPM096
| C191HM
| C192PF8
| EDL175XR
| PNA296